This is a real Callout review.
Run your own on any drawing set. 50 free credits, no card required.
AI Drawing Review Report
Riverside Office Building
Mechanical / HVACStandard ReviewM-Series_Mech_Drawings.pdfJune 12, 2025
1 CRITICAL
1 MAJOR
1 MINOR
1 ADVISORY
4 total
AI Summary
Review identified 4 comments across 4 mechanical sheets including 1 critical life-safety deficiency. The missing fire damper at Grid C-4 is a permit-blocking issue requiring immediate attention. OA separation at AHU-1 requires redesign or wind study documentation.
Codes reviewed
IMC 2024, ASHRAE 62.1-2022, NFPA 54
Sheets reviewed (4)
M-101M-201M-501M-601
PE review progress
4 / 4 reviewed (complete)
2 accepted 1 edited 1 rejected
Category:Sheet:Confidence:
CRITICALFire & Life SafetySheet: M-201
Confidence: HIGH
AcceptedDuct penetration through rated assembly lacks fire damper
IMC 2024 §607.5.1
MAJORVentilationSheet: M-101
Confidence: HIGH
EditedOA intake separation below 8′ minimum from exhaust
ASHRAE 62.1-2022 §5.7
MINORDocumentationSheet: M-601
Confidence: MEDIUM
AcceptedEquipment schedule missing operating weight for AHU-2
IMC 2024 §106.3.1
ADVISORYEnergy EfficiencySheet: M-501
Confidence: MEDIUM
RejectedVFD not specified on AHU-2 — recommend for energy compliance
ASHRAE 90.1-2022 §6.5.3
⚠ Example report only. AI-assisted review. All findings must be verified by a licensed PE before use in construction documents.