AI Drawing Review Report

Riverside Office Building

Mechanical / HVACStandard ReviewM-Series_Mech_Drawings.pdfJune 12, 2025
1 CRITICAL
1 MAJOR
1 MINOR
1 ADVISORY
4 total
AI Summary
Review identified 4 comments across 4 mechanical sheets including 1 critical life-safety deficiency. The missing fire damper at Grid C-4 is a permit-blocking issue requiring immediate attention. OA separation at AHU-1 requires redesign or wind study documentation.
Codes reviewed
IMC 2024, ASHRAE 62.1-2022, NFPA 54
Sheets reviewed (4)
M-101M-201M-501M-601
PE review progress
4 / 4 reviewed (complete)
2 accepted 1 edited 1 rejected
Category:Sheet:Confidence:
CRITICALFire & Life SafetySheet: M-201
Confidence: HIGH
Accepted
Duct penetration through rated assembly lacks fire damper
IMC 2024 §607.5.1
MAJORVentilationSheet: M-101
Confidence: HIGH
Edited
OA intake separation below 8′ minimum from exhaust
ASHRAE 62.1-2022 §5.7
MINORDocumentationSheet: M-601
Confidence: MEDIUM
Accepted
Equipment schedule missing operating weight for AHU-2
IMC 2024 §106.3.1
ADVISORYEnergy EfficiencySheet: M-501
Confidence: MEDIUM
Rejected
VFD not specified on AHU-2 — recommend for energy compliance
ASHRAE 90.1-2022 §6.5.3
Call.out
AI-powered construction drawing review. Start with 50 free credits.
Try Callout Free →
⚠ Example report only. AI-assisted review. All findings must be verified by a licensed PE before use in construction documents.