Code Reference
EnergyIECC 2021

Section C402.5/Air Leakage

IECC C402.5 covers air barrier installation, fenestration air leakage rates, and building pressurization testing.

What this section requires

The building thermal envelope must include a continuous air barrier complying with one of three options: materials with an air permeance not exceeding 0.004 cfm/sf, assemblies tested to not exceed 0.04 cfm/sf, or whole-building testing demonstrating air leakage not exceeding 0.40 cfm/sf of envelope area at 75 Pa. Fenestration products must have an air infiltration rate not exceeding 0.20 cfm/sf for operable windows and 0.04 cfm/sf for fixed windows. Loading dock weather seals and vestibules at building entrances are also addressed.

Why this section exists

Uncontrolled air leakage through the building envelope is one of the largest sources of energy waste. Air carries both sensible heat (temperature) and latent heat (moisture), making infiltration especially costly in humid climates where dehumidification energy is high. A building with good insulation but a leaky envelope wastes much of the insulation benefit. The air barrier requirement ensures that the envelope controls air movement, not just heat conduction.

What plan reviewers look for

Plan reviewers check the architectural wall sections and details for the designated air barrier material. They verify continuity at all transitions (wall-to-roof, wall-to-slab, wall-to-window). They check the fenestration schedule for air infiltration rates. They also check for vestibules at building entrances in climate zones 3 through 8 and weather seals at loading dock doors.

Common violations

Air barrier continuity not shown at transitions
Individual wall and roof sections show the air barrier but no detail connects them at the transition. The wall-to-roof and wall-to-slab joints are the most common leakage points and require explicit details.
Vestibule not provided at entrance
A building entrance in climate zone 4 or higher does not have a vestibule. The IECC requires vestibules at building entrances in climate zones 3 through 8 to reduce infiltration from door openings.
Compliance tip
Identify the air barrier on wall sections and roof details. Show continuity at every transition with sealant and membrane details. Include air infiltration rates on the fenestration schedule. Provide vestibule dimensions at entrances per climate zone requirements.

Related IECC requirements

Section C402.1 covers overall envelope requirements. Section C402.4covers fenestration thermal performance. ASHRAE 90.1 Section 5.4.3 provides equivalent air barrier requirements. Section C402.5.1 covers the specific air barrier installation requirements.

Callout automatically checks your drawings against IECC 2021 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

C402.1Building Envelope RequirementsIECC 2021C402.4FenestrationIECC 20215.4.3Air Barrier RequirementsASHRAE 90.1-2022