Code Reference
ElectricalIEEE 80-2013

Section 12/Grounding Grid Design Procedure

IEEE 80 Section 12 outlines the step-by-step procedure for designing a substation grounding grid including soil resistivity and conductor sizing.

What this section requires

The grounding grid design procedure includes: determining the maximum grid current, measuring soil resistivity, selecting the grid conductor material and size, designing the grid layout and depth, calculating the grid resistance, computing the ground potential rise (GPR), and verifying that step and touch potentials are within safe limits. The grid conductor must be sized to carry the maximum fault current for the duration of the fault without fusing. Ground rods supplement the grid to reduce resistance in high-resistivity soils.

Why this section exists

Substations handle fault currents that can reach tens of thousands of amperes. When a fault occurs, the grounding grid must safely dissipate this current into the earth without creating dangerous voltage gradients on the surface. A person standing near the substation during a fault can be electrocuted by step potential (voltage between feet) or touch potential (voltage between hands and feet when touching grounded equipment). The design procedure ensures these potentials remain within survivable limits.

What plan reviewers look for

Plan reviewers check the grounding study for soil resistivity data, grid conductor sizing calculations, GPR computation, and step and touch potential analysis. They verify the grid layout on the site plan matches the study assumptions. They check that the conductor cross- section is adequate for the fault current magnitude and clearing time.

Common violations

Soil resistivity data not site-specific
The grounding study uses assumed or generic soil resistivity instead of actual field measurements. Soil resistivity varies widely by location and directly affects the grid resistance and safety analysis.
Step and touch potentials not verified
The grounding grid layout is shown but no step and touch potential analysis is provided. Without this analysis, there is no verification that the grid meets safety criteria for personnel.
Grid conductor undersized for fault current
The grid conductor cross-section is insufficient for the maximum fault current and clearing time. The conductor must carry the fault current without exceeding its fusing temperature.
Compliance tip
Include the complete IEEE 80 grounding study with the substation drawings: soil resistivity test results, grid conductor sizing calculation, grid resistance, GPR, and step/touch potential analysis. Show the grid layout on the site plan with conductor sizes and ground rod locations.

Related IEEE 80 requirements

Section 14 covers the step and touch potential criteria. Section 11 covers soil resistivity measurement methods. NEC Section 250.50 covers grounding electrode systems. NESC covers grounding requirements for utility installations.

Callout automatically checks your drawings against IEEE 80-2013 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

23Clearances of Supply and Communication LinesNESC 202314Ground Potential RiseIEEE 80-2013250.50Grounding Electrode SystemNEC 2023