Code Reference
ElectricalNEC 2023

Section 230.70/Service Disconnecting Means

NEC 230.70 covers the location, marking, and accessibility requirements for the service disconnecting means, which must be at a readily accessible location nearest the point of entrance of service conductors.

What this section requires

The service disconnecting means must be installed at a readily accessible location nearest the point of entrance of the service conductors. It must be installed either outside the building or inside nearest the point of entrance. Section 230.70(A)(1) allows the authority having jurisdiction to require the disconnect to be located outside the building. The disconnect must be suitable for the conditions and clearly marked to identify it as the service disconnect. Per Section 230.71, a maximum of six switches or circuit breakers may serve as the service disconnect, mounted in a single enclosure or grouped at a single accessible location. Where the service disconnect is not within sight of the meter, a permanent label at the meter must indicate the location of the disconnect.

Why this section exists

The service disconnect is the last point of protection between the utility and the building's electrical system. Emergency responders must be able to locate and operate the service disconnect quickly to de-energize a building during a fire or other emergency. The "nearest the point of entrance" requirement minimizes the length of unprotected service conductors inside the building. The six-disconnect rule limits the number of switching operations needed to fully de-energize the building. Many jurisdictions now require exterior disconnects for firefighter access.

What plan reviewers look for

Plan reviewers locate the service disconnect on the electrical plan and verify it is at or near the point of service entrance. They check that the disconnect is readily accessible. They verify the disconnect is marked "Service Disconnect." They check the six-disconnect rule if multiple disconnects serve as the service. They verify the disconnect rating matches the service-entrance conductor sizing.

Common violations

Service disconnect in interior mechanical room
The main service disconnect is located in a mechanical room at the center of the building, 80 feet from the service entrance point. The disconnect must be at a readily accessible location nearest the point of entrance.
More than six service disconnects
A service switchboard has eight individual disconnects serving different portions of the building. Section 230.71 limits the service to a maximum of six disconnects.
Compliance tip
Show the service disconnect location on both the site plan and the electrical floor plan. Dimension the distance from the service entrance point. Label the disconnect "Service Disconnect" on the panel schedule and one-line diagram.
Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

230.95Ground-Fault Protection of EquipmentNEC 2023230.42Minimum Size of Service-Entrance ConductorsNEC 2023225.30Number of Supplies to a Building or StructureNEC 2023