Code Reference
ElectricalNEC 2023

Section 240.87/Arc Energy Reduction

NEC 240.87 requires arc energy reduction methods on circuit breakers rated 1200 amperes or more to reduce the severity of arc flash events.

What this section requires

Where a circuit breaker is applied to switch or protect a circuit with a trip rating of 1200 amperes or more, one or more of the following arc energy reduction methods must be provided: (1) zone-selective interlocking, (2) differential relaying, (3) an energy-reducing maintenance switching with local status indicator, (4) an energy-reducing active arc flash mitigation system, or (5) an approved equivalent means. The documentation of the available fault current required by Section 110.24 is essential for selecting and validating the arc energy reduction method. This requirement applies to all installations, not just services, and covers both new and replacement circuit breakers.

Why this section exists

Large circuit breakers (1200A and above) protect feeders and services in commercial and industrial facilities where available fault currents are high. Without arc energy reduction, the incident energy during an arc flash event at this equipment can exceed the protective capability of standard PPE. The methods listed in 240.87 reduce clearing time or arc duration: zone-selective interlocking allows a downstream breaker to signal upstream breakers to delay tripping, differential relaying detects internal faults and trips in milliseconds, maintenance switches temporarily reduce trip settings, and active arc flash mitigation systems use light sensors to detect arcs and trip instantaneously.

What plan reviewers look for

Plan reviewers identify all circuit breakers rated 1200A or more on the one-line diagram and verify that an arc energy reduction method is specified for each. They check that the selected method is noted on the drawing or in the specifications. For zone-selective interlocking, they verify the communication wiring between breakers is shown. For energy-reducing maintenance switches, they verify the local status indicator is specified. They also verify that arc flash warning labels are required at each location.

Common violations

No arc energy reduction method specified
A 2000-ampere main breaker and a 1600-ampere feeder breaker are shown on the one-line diagram with no arc energy reduction method noted for either device. Both breakers exceed the 1200-ampere threshold and require one of the five listed methods.
Method specified but not detailed on drawings
The specification references zone-selective interlocking but the electrical drawings do not show the ZSI communication wiring between the main and feeder breakers. The drawings must show how the selected method is implemented.
Compliance tip
On the one-line diagram, note the arc energy reduction method at each breaker rated 1200A or more. If using zone-selective interlocking, show the ZSI signal wiring. Coordinate with the arc flash study to confirm the selected method reduces incident energy to levels compatible with available PPE categories per NFPA 70E 130.7.
Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

110.16Arc Flash Hazard WarningNEC 2023110.24Available Fault Current DocumentationNEC 2023230.95Ground-Fault Protection of EquipmentNEC 2023

Related articles

Electrical Plan Review Checklist: 10 Issues to Catch Before Submittal