Code Reference
ElectricalNEC 2023

Section 690.12/Rapid Shutdown of PV Systems

NEC 690.12 requires rapid shutdown capability for rooftop PV systems to protect firefighters from energized DC conductors.

What this section requires

PV system circuits on or in buildings must include a rapid shutdown function that reduces conductor voltage within the array boundary to 80 volts or less within 30 seconds of rapid shutdown initiation. The initiation device must be at a readily accessible location outside the array boundary. Conductors more than 3 feet from the array or more than 1 foot inside a building must also be limited to 80 volts within 30 seconds.

Why this section exists

PV arrays generate DC voltage whenever exposed to light. Firefighters responding to a building fire with rooftop solar panels face the risk of electrocution from energized DC conductors that cannot be de-energized by simply turning off the main breaker. Rapid shutdown provides a way to reduce the voltage on rooftop conductors to safe levels so firefighters can ventilate the roof and fight the fire without electrical hazards.

What plan reviewers look for

Plan reviewers check the PV system one-line diagram for rapid shutdown equipment (module-level power electronics or other listed rapid shutdown devices). They verify that the initiation device is located at a readily accessible exterior location and that the system is designed to reduce voltage within the array to 80 volts within 30 seconds. They also check that the rapid shutdown equipment is listed for the application.

Common violations

No rapid shutdown equipment shown
The PV system one-line diagram shows string inverters and combiner boxes but no module-level rapid shutdown devices. Standard string inverter systems do not meet 690.12 without additional rapid shutdown equipment at the module level.
Initiation device location not specified
The rapid shutdown initiation device (switch or disconnect) is not shown on the drawings or is located in an area that is not readily accessible to emergency responders.
Conductors outside boundary not addressed
Rapid shutdown is provided within the array, but DC conductors running from the array to the inverter (more than 3 feet from the array or inside the building) are not addressed in the rapid shutdown design.
Compliance tip
Show the rapid shutdown equipment on the PV one-line diagram. Specify module-level power electronics (MLPEs) or other listed rapid shutdown devices. Show the initiation device location on the site plan at a readily accessible exterior location. Note the 80V / 30-second compliance on the drawings.

Related NEC requirements

Section 690.11 covers arc-fault circuit protection for PV systems. Section 690.31 covers PV system wiring methods. Section 690.41 covers system grounding. The 2023 NEC tightened the rapid shutdown requirements compared to earlier editions.

Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

110.24Available Fault Current DocumentationNEC 2023230.95Ground-Fault Protection of EquipmentNEC 2023700.12Emergency System Power SourcesNEC 2023