Code Reference
ElectricalNESC 2023

Section 25/Clearances Between Conductors

NESC Rule 25 establishes minimum clearances between supply conductors and between supply and communication conductors on the same or adjacent structures.

What this section requires

Conductors on the same supporting structure must maintain minimum vertical and horizontal separation based on their voltage levels. Supply conductors of different voltages must maintain clearances per Table 235. Communication conductors must be separated from supply conductors by the communication worker safety zone. At crossings between lines on different structures, the higher-voltage line must be positioned above the lower-voltage line with clearances per Rule 233.

Why this section exists

Conductors that swing too close together in wind or ice conditions can contact each other, causing short circuits, equipment damage, and fire. Conductors at different voltages must be separated to prevent flashover. Communication workers must be protected from accidental contact with supply conductors by maintaining a dedicated safety zone on the pole.

What plan reviewers look for

Plan reviewers check pole framing diagrams for conductor spacing at attachment points. They verify that supply and communication conductors are in the correct zones on the pole (supply above communication). They check that conductors of different voltages maintain the required separation at the pole and at mid-span under maximum sag and swing conditions.

Common violations

Insufficient separation between voltage levels
Conductors of different voltage levels on the same pole are spaced closer than the Rule 235 table requires. This is common when adding new circuits to existing poles with limited space.
Communication zone encroachment
Supply conductors are located within the communication worker safety zone, exposing communication workers to energized supply conductors during routine maintenance.
Compliance tip
Include a pole framing diagram showing conductor positions, voltages, and clearances at each pole type. Verify clearances at mid-span under maximum sag and wind swing conditions. Identify the communication worker safety zone on joint-use poles.

Related NESC requirements

Rule 23 covers clearances from ground and structures. Rule 24 covers clearances from structures and surfaces. Table 235 provides specific conductor separation values by voltage.

Callout automatically checks your drawings against NESC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

23Clearances of Supply and Communication LinesNESC 2023