Code Reference
Fire ProtectionNFPA 13 2022

Section 8.3.1/Types of Sprinkler Systems

NFPA 13 Section 8.3 defines wet pipe, dry pipe, preaction, and deluge sprinkler system types and when each is required.

What this section requires

Sprinkler systems are classified into four types. Wet pipe systems maintain water in the piping at all times and are the most common and reliable type. Dry pipe systems use pressurized air or nitrogen in the piping, with water held at a dry pipe valve until a sprinkler operates; these are required in spaces subject to freezing. Preaction systems require both a detection event and a sprinkler operation before water flows, used in areas where accidental water discharge would cause significant damage (data centers, museums). Deluge systems have open sprinklers that all discharge simultaneously when the system activates, used for high-hazard areas (aircraft hangars, chemical storage).

Why this section exists

Different environments require different sprinkler system responses. A wet pipe system in an unheated parking garage would freeze and burst. A standard wet pipe system in a data center risks accidental water discharge from a mechanical impact. A standard system in an aircraft hangar cannot suppress a fast-developing fuel fire because it waits for individual sprinklers to open sequentially. Matching the system type to the hazard ensures effective fire suppression while minimizing unintended water damage.

What plan reviewers look for

Plan reviewers check the sprinkler riser diagram and system description for the system type. They verify that wet pipe systems are not used in freezing areas. They check that preaction systems include the required detection system and supervisory features. For dry pipe systems, they verify the maximum allowable pipe volume and the water delivery time to the most remote sprinkler (60 seconds maximum for most systems).

Common violations

Wet system specified in freezing area
A wet pipe sprinkler system is shown in an unheated loading dock, parking garage, or attic space where temperatures can drop below 40 degrees F. These areas require a dry pipe or preaction system.
Preaction system without detection
A preaction system is specified but the associated fire detection system (smoke or heat detectors in the protected space) is not shown on the fire alarm drawings. Preaction systems require a detection event to charge the piping.
Compliance tip
Identify the sprinkler system type on the riser diagram and in the system description. For dry pipe systems, include the water delivery time calculation. For preaction systems, coordinate with the fire alarm design to show the detection coverage in the protected space. Clearly indicate which areas of the building are served by each system type.

Related NFPA 13 requirements

Section 8.5.1 covers sprinkler spacing for all system types. Section 7.2 covers dry pipe system specific requirements. Section 7.3 covers preaction system requirements. Section 7.4 covers deluge system requirements. Section 6.1.1 covers water supply requirements for all system types.

Callout automatically checks your drawings against NFPA 13 2022 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

8.5.1Sprinkler Spacing and CoverageNFPA 13 20226.1.1Water Supply RequirementsNFPA 13 202223.1.1Hydraulic Calculation RequirementsNFPA 13 2022

Related articles

NFPA 13 vs. 13R vs. 13D: Which Sprinkler Standard Applies to Your Project?