Code Reference
ElectricalNFPA 70E

Section 130.5/Arc Flash Risk Assessment

NFPA 70E Section 130.5 requires an arc flash risk assessment before work on or near energized electrical equipment.

What this section requires

An arc flash risk assessment must be performed before a person approaches within the arc flash boundary of energized electrical conductors or circuit parts. The assessment determines the arc flash boundary distance, the incident energy at the working distance, and the required PPE. The assessment can use either the incident energy analysis method (per IEEE 1584) or the arc flash PPE category method (Table 130.7(C)(15)(a) and (b)). The results must be documented and made available to employees.

Why this section exists

Arc flash incidents produce extreme temperatures, pressure waves, and molten metal projectiles that cause severe burns, hearing damage, and blast injuries. The risk assessment ensures that workers know the hazard level before they approach energized equipment and wear appropriate PPE rated for the potential incident energy. Without the assessment, workers may underestimate the hazard and use insufficient protection.

What plan reviewers look for

While NFPA 70E is primarily an operational standard (not a construction permit requirement), plan reviewers increasingly check for arc flash labeling notes on electrical drawings per NEC 110.16. They verify that the electrical design provides the information needed for future arc flash studies: available fault current (110.24), breaker types and settings, and the one-line diagram configuration.

Common violations

No arc flash study referenced on drawings
The electrical drawings do not reference an arc flash study or provide enough information for one to be performed. Available fault current, breaker clearing times, and system configuration are needed for the IEEE 1584 analysis.
Arc flash labels not addressed
The drawings do not include a commitment to provide arc flash labels per NEC 110.16 before equipment is energized. While the detailed NFPA 70E assessment is operational, the labeling requirement is a construction code requirement.
Compliance tip
Include available fault current on the one-line diagram (per NEC 110.24), note breaker types and settings, and reference the commitment to arc flash labeling per NEC 110.16. For industrial facilities, consider including the incident energy analysis results on the one-line diagram at the design stage.

Related requirements

NEC 110.16 requires arc flash warning labels. NEC 110.24 requires available fault current documentation. IEEE 1584 provides the calculation methodology for incident energy. Section 130.7 covers the PPE requirements based on the risk assessment results.

Callout automatically checks your drawings against NFPA 70E and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

110.16Arc Flash Hazard WarningNEC 2023110.24Available Fault Current DocumentationNEC 2023130.7Personal Protective Equipment for Arc FlashNFPA 70E