Code Reference
Fire ProtectionNFPA 72 2022

Section 10.4.1/Fire Alarm System Power Supply

NFPA 72 Section 10.4 covers primary and secondary power supply requirements for fire alarm systems including battery backup sizing.

What this section requires

Fire alarm systems must have a primary power supply from a dedicated branch circuit with no other loads. The circuit must be mechanically protected (in conduit or armored cable) and must be supplied from ahead of the main disconnect or from a source that is not controlled by a disconnect accessible to unauthorized persons. A secondary (battery) power supply must be capable of operating the system in normal supervisory mode for 24 hours and then operating all notification appliances for 5 minutes (or 15 minutes for voice evacuation systems).

Why this section exists

Fire alarm systems must operate during power outages and building emergencies when the normal power supply may be interrupted. The dedicated circuit requirement prevents a tripped breaker on a shared circuit from disabling the fire alarm. The 24-hour plus 5-minute battery requirement ensures the system operates through extended power outages and still has capacity to sound the alarm if a fire occurs during the outage.

What plan reviewers look for

Plan reviewers check the electrical panel schedule for a dedicated circuit to the fire alarm control panel (FACP). They verify that the circuit is labeled and that no other loads share it. They check the fire alarm riser diagram for the secondary power supply (batteries) and look for a battery calculation demonstrating the 24-hour plus 5-minute capacity. They also verify that the primary circuit is mechanically protected per NEC 760.

Common violations

FACP not on dedicated circuit
The fire alarm control panel is connected to a circuit that also serves other loads (lighting, receptacles). Any trip on the shared circuit disables the fire alarm system.
No battery calculation provided
The fire alarm drawings do not include a battery calculation demonstrating 24-hour standby plus 5-minute alarm capacity. Reviewers require this calculation to verify the secondary supply.
Primary circuit not mechanically protected
The dedicated fire alarm circuit runs in NM cable (Romex) instead of conduit or MC cable. NEC 760.41 and NFPA 72 require the supply circuit to be mechanically protected.
Compliance tip
Show the dedicated FACP circuit on the electrical panel schedule with a clear label ("FIRE ALARM -- DO NOT DISCONNECT"). Include a battery calculation on the fire alarm drawings showing the 24-hour standby and 5-minute alarm capacity. Specify conduit or MC cable for the supply circuit.

Related NFPA 72 requirements

Section 10.5 covers fire alarm system monitoring requirements. NEC Section 760.41 covers the supply circuit power source requirements. Section 10.6 covers the fire alarm system wiring methods. NEC Article 700 covers emergency system power supply requirements.

Callout automatically checks your drawings against NFPA 72 2022 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

700.12Emergency System Power SourcesNEC 202317.5.3Smoke Detector SpacingNFPA 72 202218.5.3Visible Notification Appliance PlacementNFPA 72 2022

Related articles

9 NFPA 72 Fire Alarm Violations That Hold Up Permits and InspectionsPre-Submittal Checklist: 12 Things to Verify Before You Submit for Permit