Code Reference
Fire ProtectionNFPA 72 2022

Section 10.6.1/Fire Alarm System Power Supply

NFPA 72 Section 10.6 covers fire alarm system power supply requirements including primary and secondary power sources, battery calculations, and transfer time.

What this section requires

Fire alarm systems must have two independent power sources: a primary supply and a secondary (standby) supply. The primary supply must be a dedicated branch circuit from a commercial power source, connected ahead of any disconnect serving the building (or, if connected downstream, provided with a mechanical lock in the on position). The secondary supply must be either storage batteries or an automatic-starting engine- driven generator with 4 hours of battery bridge power. For battery-only secondary supply, the batteries must support the system in supervisory (standby) mode for 24 hours followed by 5 minutes of alarm operation at full load. Systems with an approved generator may reduce the battery standby to 4 hours. Transfer from primary to secondary power must occur within 30 seconds and must not cause loss of signals or system functions. Battery calculations must account for all connected loads during standby (panel quiescent current, detector supervisory current, LED indicators) and during alarm (notification appliance current at maximum connected load).

Why this section exists

Fire alarm systems must be operational during power outages, which frequently coincide with emergency events (storms that cause both power failures and fires). The 24-hour standby plus 5-minute alarm requirement ensures the system can detect and announce a fire even after a full day without primary power. The dedicated circuit requirement prevents the fire alarm from being inadvertently de-energized during maintenance on other building systems. The NEC Article 760 establishes the electrical wiring requirements for these circuits, while NFPA 72 establishes the functional requirements for the power supply system as a whole.

What plan reviewers look for

Plan reviewers check the fire alarm riser diagram for the primary power source (dedicated circuit, breaker identification, lock-on provisions). They verify the secondary power source (battery or generator-with-battery-bridge) and check the battery calculation for 24 hours standby plus 5 minutes alarm. They verify the battery calculation includes all connected loads: panel standby current, initiating device supervisory current, and notification appliance alarm current. They check that the battery type and capacity are specified on the drawings. For systems with a generator backup, they verify the 4-hour battery bridge and automatic transfer switch arrangement.

Common violations

Battery calculation not provided
The fire alarm riser diagram shows batteries at the control panel but no battery calculation is included in the submittal. The calculation must demonstrate that the specified batteries can support 24 hours of standby plus 5 minutes of alarm at the total connected notification appliance load. Without the calculation, the reviewer cannot verify the batteries are adequate.
Primary power from non-dedicated circuit
The fire alarm control panel is powered from a panelboard circuit that also serves corridor lighting. The primary power must be a dedicated branch circuit that does not supply any other loads, ensuring the fire alarm is not de-energized during work on other systems.
Compliance tip
Show the primary power source on the fire alarm riser diagram with the panelboard name, breaker number, and "DEDICATED - FIRE ALARM" label. Include the battery calculation on the drawings or in the specifications, listing standby current, alarm current, battery capacity, and the resulting standby and alarm durations. Specify battery type, voltage, and amp-hour rating on the equipment schedule.
Callout automatically checks your drawings against NFPA 72 2022 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

17.5.3Smoke Detector SpacingNFPA 72 202218.5.3Visible Notification Appliance PlacementNFPA 72 2022760.41Power Source Requirements for Non-Power-Limited Fire Alarm CircuitsNEC 2023

Related articles

Fire Protection Plan Review Checklist: 10 Issues to Catch Before Submittal