Code Reference
MechanicalNFPA 90A

Section 5.3.1/Duct Smoke Detection

NFPA 90A Section 5.3 requires duct smoke detectors in air handling units exceeding 2,000 CFM to shut down fans and prevent smoke distribution.

What this section requires

Duct smoke detectors must be installed in the return air system of air handling units with a capacity exceeding 2,000 CFM, upstream of any filters and downstream of any return air connections from the served spaces. Supply duct smoke detectors are required downstream of the air handler when the unit serves more than one floor. When activated, the duct smoke detector must shut down the air handling unit to prevent distributing smoke throughout the building.

Why this section exists

An operating air handling system can distribute smoke from a fire to every space served by the system within minutes. Duct smoke detectors monitor the air stream and shut down the fan when smoke is detected, limiting the spread. Return air detectors are more common because smoke from a fire in any served space is drawn back to the air handler through the return system, concentrating at the detector location.

What plan reviewers look for

Plan reviewers check the mechanical drawings and fire alarm riser diagram for duct smoke detectors at each air handling unit exceeding 2,000 CFM. They verify the detector location (return duct, upstream of filters). They check that the detector is connected to the fire alarm system and programmed to shut down the associated air handler. They also verify supply duct detectors on multi-floor systems.

Common violations

No duct smoke detector on AHU over 2,000 CFM
An air handling unit with a capacity exceeding 2,000 CFM does not have a duct smoke detector shown on the mechanical or fire alarm drawings.
Detector in wrong location
The return air duct smoke detector is installed downstream of the filters (where smoke particles may be filtered out) instead of upstream. The detector must sense the return air before it passes through filtration.
Fan shutdown sequence not documented
The duct smoke detector is shown but the control sequence for shutting down the air handler is not documented on the fire alarm or mechanical control drawings.
Compliance tip
Show duct smoke detectors on both the mechanical duct plan and the fire alarm riser diagram. Note the detector location relative to filters and return air connections. Document the fan shutdown sequence in the control narrative. Verify the detector is connected to the building fire alarm system.

Related NFPA 90A requirements

Section 4.3 covers fire damper and smoke damper requirements. NFPA 72 Section 17.7.5 covers duct detector installation details. IMC Section 606 covers duct smoke detector requirements in the International Mechanical Code.

Callout automatically checks your drawings against NFPA 90A and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

401.2Ventilation RequiredIMC 202117.5.3Smoke Detector SpacingNFPA 72 20224.3.1Duct Construction and Fire ProtectionNFPA 90A