Code Reference
PlumbingUPC 2021

Section 610.1/Water Supply Protection (Backflow Prevention)

UPC 610 covers backflow prevention requirements including device types based on degree of hazard.

What this section requires

The potable water supply must be protected from contamination by backflow through cross-connections. The type of backflow prevention device depends on the degree of hazard. High-hazard connections (sewage, chemical systems, medical equipment) require a reduced pressure principle backflow preventer (RP) or an air gap. Low-hazard connections (fire sprinkler systems with no chemical additives, irrigation without chemical injection) may use a double check valve assembly (DC). Atmospheric vacuum breakers, pressure vacuum breakers, and hose bibb vacuum breakers are permitted for specific applications per Table 603.2 of the UPC.

Why this section exists

Backflow contamination of the potable water supply is a public health emergency. When water pressure drops (a water main break, fire hydrant use, or pump failure), contaminated water from connected non-potable systems can be siphoned back into the drinking water supply. The UPC backflow requirements parallel the IPC requirements but reference UPC-specific tables and device standards. In western US states that adopt the UPC, these provisions govern the backflow prevention design.

What plan reviewers look for

Plan reviewers identify every cross-connection on the plumbing drawings and verify the correct backflow preventer type per the UPC tables. They check the building supply for a backflow preventer if required by the water purveyor. They verify that irrigation, boiler makeup, cooling tower, and fire sprinkler connections all have appropriate devices. They also check accessibility for the annual testing required on RP and DC assemblies.

Common violations

Hose bibb without vacuum breaker
Exterior hose bibbs and laundry faucets with hose thread connections do not have vacuum breakers. A garden hose submerged in a pool of contaminated water can siphon that water into the potable supply.
RP device in inaccessible location
A reduced pressure backflow preventer is installed above a ceiling or in a confined space where annual testing and maintenance cannot be performed. RP devices require periodic testing and must be accessible.
Compliance tip
Include a backflow prevention schedule on the plumbing drawings listing each cross-connection, the hazard degree, and the required device type. Show the devices on the plumbing plan with access clearances. Verify compliance with the local water purveyor's backflow prevention requirements, which may exceed the UPC minimums.

Related UPC requirements

Table 603.2 lists the approved backflow devices by application. Section 603 covers water supply design including pressure considerations with backflow preventers. IPC Section 608 provides the equivalent backflow requirements for IPC jurisdictions. The local water purveyor may have a cross-connection control program with additional requirements.

Callout automatically checks your drawings against UPC 2021 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

603.1Water Supply System DesignUPC 2021701.1Drainage System DesignUPC 2021608.1Backflow PreventionIPC 2021