Code Reference
MechanicalASHRAE 62.1-2022

Section 6.2.3/Zone Air Distribution Effectiveness

ASHRAE 62.1 Section 6.2.3 provides the Ez factor that adjusts outdoor air based on supply air configuration (ceiling vs. floor).

What this section requires

The zone outdoor airflow must be adjusted by the zone air distribution effectiveness factor Ez from Table 6.2.3.1. The breathing zone outdoor airflow (Vbz) is divided by Ez to determine the zone outdoor airflow (Voz = Vbz / Ez). For ceiling supply with ceiling or wall return and a supply-to-room temperature differential of 15 degrees F or less, Ez = 1.0 (no adjustment). For ceiling supply with floor return delivering warm air 15 degrees F or more above room temperature, Ez = 0.8 (requiring 25% more outdoor air). For floor supply with ceiling return delivering cool air, Ez = 1.2 (allowing a 17% reduction). The factor reflects how well the supply air mixes with room air at the breathing zone height.

Why this section exists

The ventilation rate calculation assumes that outdoor air is perfectly mixed with room air at the breathing zone (4 to 6 feet above the floor). In reality, supply air distribution affects mixing. Warm air supplied from the ceiling tends to stratify above the breathing zone, delivering less outdoor air to occupants than expected. Cool air from floor diffusers rises through the breathing zone, providing better outdoor air delivery. The Ez factor corrects the calculation for these real-world distribution effects.

What plan reviewers look for

Plan reviewers check the ventilation calculation for the Ez factor at each zone. They verify the supply air configuration (ceiling vs. floor supply, ceiling vs. floor return) from the mechanical drawings. They check the supply air temperature differential to determine which Ez value applies. They verify the zone outdoor airflow is calculated as Vbz / Ez, not just Vbz.

Common violations

Ez factor omitted from calculation
The ventilation calculation uses the breathing zone rate (Vbz) directly as the zone outdoor airflow without dividing by Ez. For ceiling supply with warm air, this underestimates the required outdoor air by 25%.
Wrong Ez for supply configuration
The calculation uses Ez = 1.0 for a displacement ventilation system (floor supply, ceiling return) where Ez = 1.2 is appropriate. While this is conservative (provides more outdoor air than needed), it oversizes the system.
Compliance tip
Include the Ez factor in the ventilation calculation for each zone. Note the supply air configuration and temperature differential that determines the Ez value. Reference Table 6.2.3.1. For zones with displacement ventilation, use Ez = 1.2 to take credit for the improved air distribution.
Callout automatically checks your drawings against ASHRAE 62.1-2022 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

6.2.1Zone Outdoor Air RateASHRAE 62.1-20226.3.1System Ventilation EfficiencyASHRAE 62.1-20226.2.5Demand Control VentilationASHRAE 62.1-2022

Related articles

6 ASHRAE 62.1 Ventilation Errors That Get Flagged in Mechanical Plan Review