Code Reference
EnergyASHRAE 90.1-2022

Section 5.5.3/Opaque Envelope Insulation Requirements

ASHRAE 90.1 Section 5.5.3 establishes minimum insulation R-values and maximum U-factors for opaque envelope assemblies by climate zone.

What this section requires

Opaque building envelope assemblies (roofs, walls, floors, below-grade walls, slab-on-grade floors) must meet the insulation and U-factor requirements in Tables 5.5-1 through 5.5-8 for the applicable climate zone. The tables provide either minimum R-values for insulation alone or maximum U-factors for the entire assembly. Continuous insulation (ci) requirements are specified separately from cavity insulation. Metal building assemblies, steel-framed, wood-framed, and mass walls each have their own table with different requirements.

Why this section exists

The opaque envelope is responsible for the majority of heating and cooling energy transfer through the building skin. Insulation requirements are calibrated by climate zone because heating-dominated climates need more insulation to retain heat while cooling-dominated climates need less insulation but better solar control. The separate tables for each construction type account for the different thermal bridging characteristics of steel framing, wood framing, and mass walls.

What plan reviewers look for

Plan reviewers check wall sections, roof details, and floor assemblies for insulation types and R-values. They verify that the values meet the applicable table for the climate zone and construction type. They pay particular attention to continuous insulation requirements, which must be uninterrupted by framing, and to the distinction between above-grade and below-grade wall requirements.

Common violations

Continuous insulation missing or insufficient
The wall section shows cavity insulation only, but the climate zone and construction type require continuous insulation outboard of the framing. Steel-framed walls almost always need ci because of thermal bridging through the studs.
Wrong table used for construction type
Using the wood-framed wall table for a steel-framed wall, which has significantly different requirements due to the higher thermal conductivity of steel framing.
Below-grade wall insulation omitted
Below-grade portions of basement walls are shown without insulation. Tables 5.5-5 and 5.5-6 have specific requirements for below-grade walls that are often overlooked.
Compliance tip
Include an envelope compliance matrix on the energy code documentation showing each assembly type, construction type, applicable table, climate zone, required R-value or U-factor, and provided value. Detail continuous insulation on wall sections showing it uninterrupted across framing.

Related ASHRAE 90.1 requirements

Section 5.5.4 covers fenestration requirements. Section 5.4.3 covers air barrier requirements. Section 5.8 covers the building envelope trade-off option (COMcheck). The IECC Section C402 provides equivalent prescriptive requirements.

Callout automatically checks your drawings against ASHRAE 90.1-2022 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

C402.1Building Envelope RequirementsIECC 20215.5.4Fenestration RequirementsASHRAE 90.1-20226.4.1HVAC Equipment EfficiencyASHRAE 90.1-2022