Section 6.4.1/HVAC Equipment Efficiency
ASHRAE 90.1 Section 6.4.1 establishes minimum efficiency ratings for HVAC equipment including chillers, boilers, and heat pumps.
All HVAC equipment must meet or exceed the minimum efficiency ratings in the applicable efficiency table at the time of installation. For unitary air conditioners and heat pumps, efficiency is specified as SEER2 or EER2. For chillers, efficiency is specified as full-load kW/ton and IPLV. For boilers, efficiency is specified as thermal efficiency or combustion efficiency. Equipment must be listed by an approved agency and rated under the applicable AHRI or ASHRAE test standard.
Why this section exists
HVAC equipment efficiency has the largest single impact on building energy consumption. A chiller that operates at 0.55 kW/ton uses 10% less energy than one at 0.61 kW/ton over its lifetime. The minimum efficiency requirements ensure that all new equipment meets a reasonable performance baseline, preventing the installation of low-cost, low-efficiency equipment that wastes energy for 15-25 years.
What plan reviewers look for
Plan reviewers check the mechanical equipment schedule for efficiency ratings and compare them against the applicable table in Section 6.8.1. They verify the equipment type, capacity range, and heating type match the correct table row. They check that the rating metric (SEER2 vs. EER2 vs. IEER) matches what the table requires for that equipment type and capacity.
Common violations
Related ASHRAE 90.1 requirements
Section 6.5 covers HVAC system controls including economizers and demand control ventilation. Section 6.4.3 covers duct and piping insulation. IECC Section C403.3 provides equivalent equipment efficiency requirements. Section 6.5.1 covers economizer requirements.