Code Reference
EnergyASHRAE 90.1-2022

Section 6.5.1/Economizer Requirements

ASHRAE 90.1 Section 6.5.1 requires air-side economizers on cooling systems above 54,000 Btu/h in climate zones 2-8.

What this section requires

Air-side economizers are required on individual cooling systems with a cooling capacity of 54,000 Btu/h or greater in climate zones 2 through 8. The economizer must be capable of providing 100 percent outdoor air to the supply when outdoor conditions are favorable. High-limit shutoff controls must be provided to disable the economizer when outdoor conditions exceed the economizer setpoint. Water-side economizers are permitted as an alternative in some climate zones. Exceptions apply to certain system types including dedicated outdoor air systems and systems with energy recovery.

Why this section exists

During mild weather, the outdoor air temperature is lower than the return air temperature from the building. An economizer opens the outdoor air damper to use this free cooling instead of running the mechanical cooling system. In many climates, economizer operation can reduce cooling energy by 20-40% annually. Without the requirement, systems would default to mechanical cooling even when free cooling is available, wasting energy.

What plan reviewers look for

Plan reviewers check the mechanical equipment schedules and control sequences for economizer capability on every cooling system at or above 54,000 Btu/h. They verify the high-limit shutoff type (differential dry-bulb or differential enthalpy, depending on climate zone per Table 6.5.1.1.3). They check that the outdoor air damper is sized for 100% outdoor air when economizing.

Common violations

No economizer on qualifying system
A rooftop unit with 60,000 Btu/h cooling in climate zone 4 does not include an economizer. The economizer threshold is 54,000 Btu/h in climate zones 2 through 8.
High-limit shutoff type wrong for climate zone
The control sequence specifies a fixed dry-bulb high limit when the climate zone requires differential enthalpy control per Table 6.5.1.1.3. Using the wrong control type reduces the economizer operating hours.
Compliance tip
Note economizer capability and high-limit control type on the mechanical equipment schedule for every cooling system at or above 54,000 Btu/h. Reference Table 6.5.1.1.3 for the correct high-limit type. Include economizer operation in the control sequence of operations.

Related ASHRAE 90.1 requirements

Section 6.4.1 covers equipment efficiency. Section 6.5.2 covers simultaneous heating and cooling limitations. Section 6.5.3 covers air system design and control. IECC Section C403.5 provides equivalent economizer requirements.

Callout automatically checks your drawings against ASHRAE 90.1-2022 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

C403.1Mechanical Systems ScopeIECC 20215.5.3Opaque Envelope Insulation RequirementsASHRAE 90.1-20226.4.1HVAC Equipment EfficiencyASHRAE 90.1-2022