Section 6.5.3/Air System Design and Control
ASHRAE 90.1 Section 6.5.3 covers VAV controls, fan power limitations, and simultaneous heating and cooling restrictions.
Multi-zone HVAC systems with a total fan system power exceeding specified thresholds must use variable air volume (VAV) fan control. Fan power is limited by Section 6.5.3.1 based on the system configuration and airflow. Zone-level controls must modulate airflow to match the load rather than using constant volume with reheat, which wastes energy by simultaneously cooling and reheating air. Reheat is limited: single-duct VAV systems must reduce airflow to the minimum before energizing reheat. Dual-duct and multizone systems must comply with the simultaneous heating and cooling limitations of Section 6.5.2.
Why this section exists
Air distribution accounts for a significant portion of HVAC energy use. A constant-volume system that cools all air to 55 degrees and then reheats it at each zone wastes enormous energy. VAV systems save 30-50% of fan energy by reducing airflow when zones are at partial load. Fan power limits prevent designers from oversizing fans, which wastes energy even on VAV systems. These provisions address the largest single category of HVAC energy waste in commercial buildings.
What plan reviewers look for
Plan reviewers check the mechanical drawings for VAV terminal units at each zone. They verify that the air handling unit has a variable frequency drive (VFD) on the supply fan. They check the control sequence for the VAV box minimum airflow setpoints and the reheat sequence (airflow must reduce before reheat activates). They also verify that the total fan brake horsepower does not exceed the fan power limitation.
Common violations
Related ASHRAE 90.1 requirements
Section 6.5.1 covers economizer requirements. Section 6.5.2 covers simultaneous heating and cooling limitations. Section 6.4.1 covers equipment efficiency. Section 6.5.3.1 provides the fan power limitation formulas.