Code Reference
ArchitecturalIBC 2021

Section 1006.2/Minimum Number of Exits

IBC 1006.2 establishes the minimum number of exits required from each story and from individual spaces, based on occupant load thresholds.

What this section requires

Each story must be served by the minimum number of exits per Table 1006.3.4: one exit for occupant loads of 1 to 500 (with limitations), two exits for 1 to 500 without limitations, three exits for 501 to 1000, and four exits for more than 1000 occupants. Individual spaces with occupant loads exceeding the Table 1006.2.1 threshold for the occupancy type must have at least two exit access doorways.

Why this section exists

Multiple exits ensure that building occupants have alternate escape routes if one exit is blocked by fire, smoke, or structural failure. The occupant load thresholds reflect the risk: higher occupant loads require more exits because more people competing for fewer exits increases evacuation time and the likelihood of crowding at exit points.

What plan reviewers look for

Plan reviewers calculate the occupant load for each story and each individual space, then verify that the floor plan shows the required number of exits. They also check exit separation distance: where two exits are required, they must be separated by at least one-half the maximum overall diagonal dimension of the building or area served (one-third if sprinklered).

Common violations

Single exit from a space requiring two
A conference room, assembly space, or classroom with an occupant load exceeding the Table 1006.2.1 threshold has only one door. Two exit access doorways are required.
Exit separation distance not met
Two exits are provided but they are located close together on the same wall, failing the one-half diagonal separation requirement. This defeats the purpose of having two exits if both can be blocked by the same event.
Single exit story without meeting exceptions
A story is shown with only one exit but does not meet the conditions required for single-exit stories in Table 1006.3.4, such as occupant load limits, common path of travel limits, and travel distance limits.
Compliance tip
Show the occupant load for each space and each story on the floor plan. Dimension the exit separation distance and note the diagonal dimension used. For single-exit stories, document compliance with every condition in Table 1006.3.4 in the code analysis.

Related IBC requirements

Section 1004.1 establishes the occupant load that drives exit count.Section 1005.1 determines the minimum width of each exit. Section 1017 covers corridor requirements. Section 1007 covers exit configuration and separation distance requirements.

Callout automatically checks your drawings against IBC 2021 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

1004.1Occupant Load CalculationIBC 20211005.1Minimum Egress WidthIBC 20211017.2Exit Access Travel DistanceIBC 2021

Related articles

10 IBC Egress Violations That Show Up in Every Drawing Review