Code Reference
ArchitecturalIBC 2021

Section 1017.2/Exit Access Travel Distance

IBC 1017.2 and Table 1017.2 set maximum travel distances from any point in a building to the nearest exit, varying by occupancy and sprinkler protection.

What this section requires

The exit access travel distance from any occupied point to the nearest exit must not exceed the values in Table 1017.2. For most sprinklered business (Group B) occupancies, the maximum is 300 feet. Without sprinklers, the limit drops to 200 feet. Assembly occupancies with sprinklers allow 250 feet. High-hazard and storage occupancies have shorter limits. Travel distance is measured along the natural path of egress, not as a straight line.

Why this section exists

Travel distance limits ensure that occupants can reach an exit before being overcome by fire, smoke, or heat. The limits are based on research into occupant walking speed, fire growth rates, and the time available before conditions become untenable. Sprinklered buildings get longer travel distances because the sprinkler system controls fire growth and extends the available safe egress time.

What plan reviewers look for

Plan reviewers measure the travel distance from the most remote point in each space to the nearest exit along the path of travel (through aisles, corridors, around furniture, and through doors). They verify the correct occupancy group and sprinkler status are used to select the allowable travel distance from Table 1017.2. Dead-end corridors are measured separately under Section 1020.4.

Common violations

Travel distance measured as straight line
The travel distance is measured as a straight-line distance from the remote point to the exit instead of along the actual path of travel. The path must account for furniture, walls, aisles, and corridor routing.
Unsprinklered distance used for sprinklered building
The code analysis uses the shorter unsprinklered travel distance limit when the building is sprinklered, unnecessarily constraining the design. More commonly, the reverse: using the sprinklered limit for an unsprinklered building.
Remote point not identified
The drawings do not show where the most remote point is or document the longest travel distance. Without this, the reviewer must measure it themselves, which often results in a comment requesting the information.
Compliance tip
Dimension the travel distance from the most remote point on each floor to the nearest exit. Show the travel path on the floor plan. Note the allowable distance from Table 1017.2, the occupancy group, and the sprinkler status in the code analysis.

Related IBC requirements

Section 1006.2 determines the minimum number of exits. Section 1020.4 limits dead-end corridor length (20 feet unsprinklered, 50 feet sprinklered for most occupancies). Section 903.2 determines when sprinklers are required, which directly affects the allowable travel distance.

Callout automatically checks your drawings against IBC 2021 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

903.2Where Sprinkler Systems Are RequiredIBC 20211004.1Occupant Load CalculationIBC 20211006.2Minimum Number of ExitsIBC 2021

Related articles

10 IBC Egress Violations That Show Up in Every Drawing Review