Code Reference
ArchitecturalIBC 2021

Section 1207.2/Airborne Sound Transmission (STC Ratings)

IBC 1207.2 requires walls and floor-ceiling assemblies between dwelling units to achieve a minimum Sound Transmission Class (STC) of 50 laboratory or ASTC 45 field tested.

What this section requires

Walls, partitions, and floor-ceiling assemblies separating dwelling units from each other or from public and service areas must have a Sound Transmission Class (STC) of not less than 50 when tested in a laboratory per ASTM E90, or an Apparent Sound Transmission Class (ASTC) of not less than 45 when field tested per ASTM E336. This applies to all multifamily housing including apartments, condominiums, townhouses, hotels, and dormitories. Penetrations through sound-rated assemblies for electrical outlets, plumbing, HVAC ducts, and other services must be sealed, lined, insulated, or otherwise treated to maintain the required STC rating. The requirement applies to the entire assembly, not just the wall or floor material. Section 1207.3 separately requires Impact Insulation Class (IIC) 50 (lab) or AIIC 45 (field) for floor- ceiling assemblies between dwelling units.

Why this section exists

Sound transmission between dwelling units is the most common complaint in multifamily housing and a leading cause of tenant dissatisfaction. Airborne sound includes speech, music, television, and general activity noise. The STC 50 laboratory rating provides adequate speech privacy between units: loud speech can be faintly heard but is not intelligible. The 5-point reduction allowed for field testing (ASTC 45 vs STC 50) accounts for flanking paths, construction tolerances, and real-world conditions that reduce performance compared to laboratory testing. The field test option provides a compliance path for verifying as-built performance.

What plan reviewers look for

Plan reviewers check wall and floor assembly specifications for documented STC ratings. They verify the specified assembly matches a tested configuration from a recognized source (such as the Gypsum Association's Fire Resistance and Sound Control Design Manual or UL's Fire Resistance Directory). They check for penetrations through rated assemblies and verify that sealing details are provided. Common flanking paths they check include back-to-back electrical outlet boxes (which must be staggered and sealed), medicine cabinets, HVAC duct penetrations, and plumbing penetrations through fire-rated assemblies that also carry sound.

Common violations

STC rating not documented for demising wall
The wall type schedule shows a demising wall between apartment units with a 1-hour fire rating but does not specify the STC rating. Fire-rated assemblies do not automatically meet the STC 50 requirement. The assembly must be specifically tested and documented to achieve both the fire rating and the sound rating.
Back-to-back electrical outlets not addressed
Electrical outlets are shown in the same stud bay on opposite sides of a demising wall. Back-to-back outlets create a direct sound flanking path that can reduce the assembly STC by 10 or more points. Outlets must be staggered to different stud bays and sealed with putty pads or acoustical sealant.
Compliance tip
Include the STC rating on every wall and floor assembly in the wall type schedule. Reference the tested assembly source (GA manual number, UL design number, or manufacturer test report). Provide details for sealing penetrations through sound-rated assemblies. Specify staggered outlet locations on demising walls. Consider specifying field testing (ASTC 45) as a verification requirement in the specifications.
Callout automatically checks your drawings against IBC 2021 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

602.2Types of ConstructionIBC 2021302.1Occupancy ClassificationIBC 2021714.1Penetrations of Fire-Resistance-Rated AssembliesIBC 2021