Code Reference
StructuralIBC 2021

Section 722.1/Calculated Fire Resistance

IBC 722 permits fire-resistance ratings to be determined by calculation methods in addition to standard fire test (ASTM E119), covering concrete, steel, wood, and masonry assemblies.

What this section requires

IBC 722 provides calculation methods for determining fire-resistance ratings as an alternative to laboratory testing per ASTM E119. Section 722.2 covers concrete assemblies, where the rating is based on the equivalent thickness of concrete and the type of aggregate. Section 722.3 covers steel assemblies, where the rating is based on the weight-to-heated-perimeter ratio (W/D) and spray-applied fireproofing thickness. Section 722.5 covers wood assemblies using the component additive method (CAM), which sums contributions of the membrane (gypsum board), framing, and insulation. Section 722.4 covers masonry. These calculated ratings are used when the actual assembly does not exactly match a tested design, allowing the designer to demonstrate compliance through engineering analysis referenced to Table 601 requirements.

Why this section exists

Standard fire tests are expensive and test only specific assemblies. When an actual construction assembly differs from a tested design, calculated fire resistance provides a code-compliant path to demonstrate the required rating without retesting. For concrete, the critical factor is heat transmission through the material thickness. For steel, the critical factor is the time to reach the critical temperature (1000 degrees F for columns, 1100 degrees F for beams) based on the mass of steel relative to the exposed surface area.

What plan reviewers look for

Plan reviewers check the construction type and verify that fire-resistance-rated assemblies are documented with either a tested design (UL design number, GA manual number) or a calculated rating per Section 722. For concrete assemblies, they check the equivalent thickness against Table 722.2.1.1 for the aggregate type. For steel, they verify the W/D ratio and fireproofing thickness. For wood, they check the component additive method against Table 722.5.1.

Common violations

Concrete slab thickness insufficient for rating
A 4.5-inch normal-weight siliceous aggregate concrete slab is specified as a 2-hour floor assembly. Table 722.2.1.1 requires 5.0 inches of siliceous aggregate concrete for a 2-hour rating.
Calculated rating not documented
The wall type schedule states "2-hour fire-rated" for a concrete masonry wall but provides no UL design number or Section 722 calculation reference. The rating must be documented with either a tested assembly reference or a calculation.
Compliance tip
For each rated assembly, note whether the rating is based on a tested design (with UL or GA reference number) or a calculation per Section 722. For concrete, specify the aggregate type and equivalent thickness. For steel, specify the W/D ratio and fireproofing type and thickness.
Callout automatically checks your drawings against IBC 2021 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

602.2Types of ConstructionIBC 2021Table 601Fire-Resistance Rating RequirementsIBC 2021714.1Penetrations of Fire-Resistance-Rated AssembliesIBC 2021

Related articles

IBC Fire-Resistance Rated Construction: What Plan Reviewers Check First