Code Reference
ElectricalIEEE 998-2012

Section 5/Electrogeometric Model Application

IEEE 998 Section 5 covers applying the electrogeometric model for substation shielding including striking distance calculations and shield wire geometry.

What this section requires

The electrogeometric model relates the striking distance to the stroke current through an empirical equation. For a given design stroke current (typically 5-10 kA for substations), the striking distance determines the radius of the arc that a downward leader can bridge to reach a grounded object. Shield wires and masts must be positioned so that their striking distance sphere overlaps the protected equipment, ensuring the leader terminates on the shield system rather than the equipment.

Why this section exists

The EGM provides the most physically accurate model of the lightning attachment process. Unlike the fixed-angle empirical method, the EGM accounts for the fact that smaller stroke currents have shorter striking distances and are harder to intercept. The design stroke current is selected based on the BIL of the protected equipment: only strokes large enough to cause a backflashover need to be intercepted, as smaller strokes are handled by the station's insulation.

What plan reviewers look for

Plan reviewers check the EGM analysis for the striking distance equation used, the design stroke current, and the geometric verification that shield wires and masts provide complete coverage. They verify the shield wire heights, sag at maximum temperature, and mast locations shown on the substation plan and elevation drawings match the EGM study inputs.

Common violations

Shield wire sag not accounted for
The shielding analysis uses the shield wire height at the attachment point but does not account for the wire sag at mid-span. At maximum sag (highest temperature), the effective shield height is lower and the protected zone shrinks.
Design stroke current not documented
The shielding study shows protected zones but does not state the design stroke current or explain how it was selected relative to the equipment BIL.
Compliance tip
Document the design stroke current, the striking distance equation, and the resulting striking distance in the shielding study. Show shield wire heights at both the attachment point and at mid-span sag. Verify coverage at mid-span sag conditions, not just at the poles.

Related IEEE 998 requirements

Section 4 introduces the three shielding methods. Section 6 covers shielding of GIS (gas-insulated switchgear) substations. IEEE 80 covers the grounding system that works with the shielding system. IEEE 1243 covers shielding of transmission lines.

Callout automatically checks your drawings against IEEE 998-2012 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

12Grounding Grid Design ProcedureIEEE 80-201314Ground Potential RiseIEEE 80-20134Lightning Shielding MethodsIEEE 998-2012