Code Reference
ElectricalNEC 2020

Section 210.8/GFCI Protection (2020 Edition)

NEC 2020 Section 210.8 expanded GFCI requirements from 2017, adding kitchens, dishwashers, and outdoor public spaces.

What this section requires

The NEC 2020 expanded GFCI requirements significantly from the 2017 edition. Section 210.8(A) for dwellings added 250-volt outlets in garages and basements, and clarified outdoor requirements. Section 210.8(B) for other-than-dwellings added kitchens in all occupancies, dishwasher branch circuits, and sinks where receptacles are within 6 feet. The 2020 edition also introduced 210.8(F) requiring GFCI for outdoor outlets in public spaces. Note: the 2023 NEC further expanded 210.8 with 150-volt-to-ground thresholds and additional locations.

Key differences from NEC 2023

The 2023 NEC expanded 210.8 further by lowering the voltage threshold from 150 volts to ground to include 208Y/120V systems more explicitly, adding outdoor patios and decks for commercial buildings, and expanding GFCI requirements for 250-volt receptacles. Jurisdictions still on the 2020 NEC use the 2020 requirements, which are less expansive than 2023 but more expansive than 2017.

What plan reviewers look for

Plan reviewers verify which NEC edition the jurisdiction has adopted. Under the 2020 NEC, they check for GFCI on all kitchen receptacles (not just countertop), bathroom, garage, outdoor, crawl space, unfinished basement, laundry, and boathouse receptacles. For commercial kitchens, they verify dishwasher circuits and sink-adjacent receptacles have GFCI protection.

Common violations

Kitchen dishwasher circuit without GFCI
The 2020 NEC added dishwasher branch circuits to the GFCI requirement in commercial kitchens. Projects under the 2020 NEC must provide GFCI on dishwasher circuits, which was not required under the 2017 edition.
Using 2023 requirements in 2020 jurisdiction
The electrical design references 2023 NEC section numbers or requirements that do not exist in the 2020 edition. Always verify the adopted edition before determining GFCI requirements.
Compliance tip
Confirm the adopted NEC edition with the jurisdiction before determining GFCI locations. Mark all GFCI-protected circuits on the panel schedule. For the 2020 NEC, pay particular attention to the expanded kitchen and dishwasher requirements that were new in that edition.
Callout automatically checks your drawings against NEC 2020 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

210.8GFCI Protection RequirementsNEC 2023210.12Arc-Fault Circuit-Interrupter ProtectionNEC 2023110.24Available Fault Current Documentation (2020 Edition)NEC 2020