Code Reference
ElectricalNEC 2023

Section 215.2/Feeder Conductor Sizing

NEC 215.2 establishes minimum feeder conductor sizing requirements including the 125 percent continuous load factor that frequently affects commercial electrical designs.

What this section requires

Feeder conductors must have an ampacity not less than the load served. Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the conductor ampacity must be not less than the noncontinuous load plus 125 percent of the continuous load. The feeder size must also meet the minimum required by the load calculation methods in Article 220.

Why this section exists

Feeders carry the aggregate load from multiple branch circuits and are critical links in the electrical distribution system. Conductors carrying continuous loads (expected to run for 3 hours or more) generate more sustained heat. The 125 percent multiplier provides a thermal safety margin and matches the overcurrent device listing requirements for continuous operation.

What plan reviewers look for

Plan reviewers check feeder conductor sizes on the riser diagram and panel schedules against the load calculations. They verify that the 125 percent continuous load factor is applied to lighting and other continuous loads. They also check for voltage drop documentation on long feeder runs.

Common violations

Continuous load factor not applied
A feeder to a lighting panel in a commercial building is sized for the calculated load without the 125% multiplier. Commercial lighting is typically a continuous load.
Load calculation not provided
The feeder size is specified on the one-line diagram but no supporting load calculation is documented for the reviewer to verify the sizing.
Voltage drop not addressed on long runs
A feeder exceeds 100 feet with no voltage drop calculation shown. While the NEC informational note recommends limiting feeder voltage drop to 3%, many jurisdictions require documentation.
Compliance tip
Include a feeder load calculation for each panel. Apply the 125% continuous load factor to lighting and similar loads. For feeders longer than 100 feet, include a voltage drop calculation referencing the informational note in 215.2(A)(3).

Related NEC requirements

Article 220 covers load calculation methods. Section 210.19 covers branch circuit conductor sizing with the same 125% continuous load requirement. Section 240.4 covers overcurrent protection. Table 310.16 provides conductor ampacity values.

Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

240.4Protection of ConductorsNEC 2023210.19Branch Circuit Conductor Minimum SizeNEC 2023