Code Reference
ElectricalNEC 2023

Section 240.4/Protection of Conductors

NEC 240.4 requires conductors to be protected against overcurrent in accordance with their ampacity, with absolute limits for small conductors.

What this section requires

Conductors must be protected against overcurrent in accordance with their ampacities. For 14 AWG copper, overcurrent protection must not exceed 15 amps; for 12 AWG, 20 amps; for 10 AWG, 30 amps. These limits apply even when the ampacity from Table 310.16 might be higher due to conductor insulation temperature rating.

Why this section exists

Without proper overcurrent protection, conductors can overheat and ignite surrounding materials. The overcurrent device must trip before the conductor reaches unsafe temperatures. The small conductor limits (14, 12, 10 AWG) provide absolute caps that prevent designers from using higher-temperature-rated insulation to justify larger breakers on small wires.

What plan reviewers look for

Plan reviewers verify that every conductor on the panel schedule is protected by an overcurrent device equal to or less than its ampacity. They specifically check the small conductor limits and verify that the next-standard-size-up rule in 240.4(B) is applied correctly when used.

Common violations

14 AWG on 20-amp breaker
14 AWG copper conductors are shown on a 20-amp circuit. Regardless of insulation type, 14 AWG is limited to 15-amp overcurrent protection.
Conductor ampacity exceeded by breaker
A feeder conductor rated for 60 amps (after derating for conduit fill or ambient temperature) is protected by an 80-amp breaker. The overcurrent device must not exceed the derated ampacity.
Next size up rule misapplied
Using the next standard size up per 240.4(B) on a circuit that supplies multiple receptacle outlets, where this exception is not permitted.
Compliance tip
Verify every circuit on the panel schedule: breaker size must not exceed the conductor ampacity from Table 310.16 after all derating factors are applied. Apply the absolute limits (15A/20A/30A) for 14/12/10 AWG regardless of insulation temperature rating.

Related NEC requirements

Table 310.16 provides conductor ampacity values. Section 240.6 lists standard overcurrent device ratings. Section 210.19 covers branch circuit conductor sizing. Section 240.21 covers tap conductor overcurrent protection rules.

Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

310.16Conductor Ampacity TableNEC 2023210.19Branch Circuit Conductor Minimum SizeNEC 2023240.6Standard Ampere RatingsNEC 2023