Code Reference
ElectricalNEC 2023

Section 310.16/Conductor Ampacity Table

NEC Table 310.16 provides conductor ampacity values by size, insulation type, and temperature rating. It is the most referenced table in the NEC.

What this section requires

Table 310.16 lists allowable ampacities of insulated conductors rated up to 2000 volts in raceways, cables, and earth, based on an ambient temperature of 30 degrees Celsius. Ampacities are provided at three temperature ratings: 60, 75, and 90 degrees Celsius. The table applies to installations with no more than three current-carrying conductors in a raceway or cable.

Why this section exists

This table is the foundational reference for conductor sizing in the NEC. It establishes the maximum continuous current a conductor can safely carry without exceeding its insulation temperature rating. The three temperature columns reflect different insulation types and equipment terminal ratings. The correct column depends on both the conductor insulation and the connected equipment per 110.14(C).

What plan reviewers look for

Plan reviewers cross-reference every conductor size on the panel schedule against Table 310.16 to verify adequate ampacity. They check which temperature column was used and verify it matches the equipment terminal ratings per 110.14(C). They look for required derating adjustments for ambient temperature and conduit fill.

Common violations

Using 90-degree column without justification
Conductors sized using the 90-degree ampacity column but terminated on equipment with 75-degree rated terminals. The 75-degree column must control unless the 90-degree column is used only to apply derating factors per 310.15.
No conduit fill adjustment
More than three current-carrying conductors in a conduit without applying the adjustment factors from Table 310.15(C)(1). Four to six conductors require an 80% adjustment; seven to nine require 70%.
No ambient temperature correction
Conductors installed in high-temperature environments (mechanical rooms, rooftops, attics) without the ambient temperature correction factor from Table 310.15(B)(1).
Compliance tip
Note the temperature rating column used for conductor sizing in the electrical general notes. Apply conduit fill adjustments when more than three current-carrying conductors share a raceway. Apply ambient temperature corrections for locations above 86 degrees Fahrenheit. Document all adjustments in the panel schedule or load calculations.

Related NEC requirements

Section 110.14(C) determines which temperature column applies based on equipment terminal ratings. Section 310.15 provides ambient temperature and conduit fill adjustment tables. Section 240.4 covers overcurrent protection requirements for the sized conductors.

Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

110.14Electrical ConnectionsNEC 2023240.4Protection of ConductorsNEC 2023210.19Branch Circuit Conductor Minimum SizeNEC 2023

Related articles

8 NEC Violations That Show Up on Every Electrical Plan Review