Code Reference
ElectricalNEC 2023

Section 220.12/Lighting Load Calculations

NEC 220.12 and Table 220.12 establish minimum lighting load values per square foot by occupancy type, forming the basis for branch circuit and feeder sizing.

What this section requires

The general lighting load must be not less than the values in Table 220.12, which provides unit lighting loads in volt-amperes per square foot by occupancy type. Dwelling units require 3 VA per square foot. Office buildings require 3.5 VA per square foot. Warehouses require 0.25 VA per square foot. Hospitals require 2 VA per square foot. The floor area is computed from the outside dimensions of the building, not the usable area.

Why this section exists

The general lighting load establishes the minimum electrical capacity that must be provided regardless of the actual lighting fixtures specified. This prevents undersized electrical systems when fixtures are changed during the building's life. An office designed with efficient LED lighting today might be retrofitted with higher-wattage fixtures in the future. The Table 220.12 values represent a reasonable minimum that accommodates typical fixture changes.

What plan reviewers look for

Plan reviewers check the electrical load calculation for the general lighting load. They verify that the correct occupancy type from Table 220.12 is used, that the floor area is based on outside dimensions, and that the total VA matches or exceeds the table value times the area. They also check that the lighting load is included in the feeder and service calculations.

Common violations

Wrong occupancy type for Table 220.12
Using the warehouse rate (0.25 VA/sf) for a mixed-use building that includes office or retail space, which have higher requirements.
Usable area used instead of outside dimensions
The lighting load calculation uses the net interior area instead of the gross area computed from outside building dimensions, resulting in a lower calculated load.
Compliance tip
Show the general lighting load calculation on the electrical drawings: building area (from outside dimensions), occupancy type from Table 220.12, unit load (VA/sf), and total general lighting VA. For multi-use buildings, apply the correct rate to each area.

Related NEC requirements

Section 210.11 covers the number of branch circuits required based on the calculated load. Section 215.2 covers feeder sizing. Section 220.14 covers receptacle outlet loads that are added to the general lighting load. Section 220.42 covers the demand factor reductions for lighting.

Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

210.11Branch Circuits RequiredNEC 2023215.2Feeder Conductor SizingNEC 2023