Code Reference
ElectricalNEC 2023

Section 250.119/Identification of Equipment Grounding Conductors

NEC 250.119 specifies how equipment grounding conductors must be identified: bare, green, or green with yellow stripes, with re-identification permitted for conductors larger than 6 AWG.

What this section requires

Equipment grounding conductors (EGCs) must be identified by one of three methods: a bare conductor (no insulation), a conductor with continuous green insulation, or a conductor with continuous green insulation with one or more yellow stripes. For conductors larger than 6 AWG, the conductor is permitted to be permanently identified as an EGC at each end and at every point where the conductor is accessible by stripping the insulation, coloring the exposed insulation green, or marking the exposed insulation with green tape or green adhesive labels. Conductors with green insulation or green with yellow stripes must not be used for any purpose other than equipment grounding. The identification must be permanent and visible at all termination and splice points.

Why this section exists

Correct identification of the equipment grounding conductor is critical for electrical safety. An EGC that is confused with a circuit conductor during installation or maintenance could result in a grounding path being used to carry load current, or a circuit conductor being connected to equipment enclosures. Either error creates electrocution risk. The dedicated green color coding ensures that electricians and maintenance personnel can immediately identify the grounding conductor. The re-identification provision for conductors larger than 6 AWG is practical because large green conductors are not stocked by most suppliers, and field identification with tape or paint is accepted practice.

What plan reviewers look for

Plan reviewers check conductor schedules and panel schedules for EGC identification. They verify that the EGC is listed separately from the neutral (grounded) conductor and that the color coding is specified correctly. For feeders and branch circuits, they verify the EGC is sized per Table 250.122 and identified per 250.119. For conductors larger than 6 AWG that will be re-identified in the field, they check that the specification calls out the re-identification method. They verify that no other conductor in the system uses green insulation.

Common violations

EGC color not specified for large feeders
A feeder schedule shows a 3/0 copper EGC but does not specify the insulation color or re-identification method. Since green-insulated 3/0 conductors are not commonly available, the specification must call out field re-identification (green tape at each end and accessible point) per 250.119.
Green conductor used as an ungrounded conductor
A branch circuit schedule shows a green-insulated conductor used as a switch leg. Green and green with yellow stripe insulation is reserved exclusively for equipment grounding conductors and must not be used for any other purpose.
Compliance tip
In conductor schedules and panel schedules, specify the EGC as "green" or "bare." For conductors larger than 6 AWG, add a note specifying the field re-identification method (e.g., "EGC: #2 Cu, re-identified green at each end per 250.119"). Include the EGC in every feeder and branch circuit listing on the panel schedule.
Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

200.6Neutral Conductor IdentificationNEC 2023250.122Equipment Grounding Conductor SizingNEC 2023250.104Bonding of Piping Systems and Exposed Structural SteelNEC 2023

Related articles

8 NEC Violations That Show Up on Every Electrical Plan Review