Code Reference
ElectricalNEC 2023

Section 250.122/Equipment Grounding Conductor Sizing

NEC 250.122 and Table 250.122 establish equipment grounding conductor sizing based on the overcurrent device rating, with a proportional upsizing requirement.

What this section requires

Equipment grounding conductors must be sized not smaller than shown in Table 250.122 based on the overcurrent device rating. Where circuit conductors are adjusted in size for voltage drop or other reasons, the equipment grounding conductor must be proportionally adjusted upward using the same ratio.

Why this section exists

The equipment grounding conductor must carry fault current long enough for the overcurrent device to clear the fault. If the EGC is too small, it can overheat and lose continuity before the breaker trips, leaving equipment enclosures energized. The proportional upsizing requirement ensures that the EGC maintains the same relative impedance when circuit conductors are increased.

What plan reviewers look for

Plan reviewers cross-reference every circuit's EGC size against Table 250.122 and the overcurrent device rating. They check for proportional upsizing when circuit conductors have been increased beyond the minimum required, which is common on long feeder runs designed for voltage drop.

Common violations

EGC undersized per Table 250.122
The equipment grounding conductor is smaller than the minimum required by Table 250.122 for the overcurrent device rating on the circuit.
EGC not proportionally adjusted
Circuit conductors are upsized from the minimum (e.g., 3 AWG to 1 AWG for voltage drop), but the EGC remains at the minimum table size instead of being proportionally increased.
EGC missing from feeder schedule
The feeder schedule shows phase and neutral conductor sizes but omits the equipment grounding conductor size entirely.
Compliance tip
Include the EGC size on every circuit in the panel schedule and feeder schedule. When conductors are upsized for voltage drop, show the proportional EGC calculation: (upsized conductor area / minimum conductor area) times the minimum EGC area from Table 250.122.

Related NEC requirements

Section 250.119 covers EGC identification. Section 250.118 lists permitted EGC types (wire, conduit, cable tray, etc.). Section 250.4 provides the general grounding requirements. Table 250.66 covers grounding electrode conductor sizing (different from EGC sizing).

Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

240.4Protection of ConductorsNEC 2023

Related articles

8 NEC Violations That Show Up on Every Electrical Plan ReviewElectrical Plan Review Checklist: 10 Issues to Catch Before Submittal