Code Reference
ElectricalNEC 2023

Section 348.10/Uses Permitted for Flexible Metal Conduit (FMC)

NEC 348.10 and 348.12 define where flexible metal conduit (FMC) is permitted and prohibited, including limitations on length and grounding path.

What this section requires

Flexible metal conduit (FMC) is permitted in exposed and concealed locations where flexibility is needed or where installation conditions make rigid conduit impractical. Common uses include final connections to motors, transformers, vibrating equipment, recessed luminaires, and HVAC equipment. Section 348.12 prohibits FMC in wet locations (unless the conductors are approved for wet locations and the installation prevents water from entering the enclosure), in hoistways, in storage battery rooms, in hazardous locations (except as permitted in Articles 501 through 504), and where subject to physical damage. FMC is permitted as an equipment grounding conductor only when the total length of FMC in the ground-fault return path does not exceed 6 feet and the circuit overcurrent device does not exceed 20 amperes per Section 250.118(5). For circuits over 20 amperes or FMC runs over 6 feet, a separate equipment grounding conductor must be installed per Section 250.122.

Why this section exists

Flexible metal conduit provides mechanical protection for conductors while allowing the flexibility needed for connections to vibrating equipment, adjustable fixtures, and equipment that must be moved for servicing. The flexibility comes from the interlocking spiral metal strip construction, but this same construction creates higher impedance in the ground-fault return path compared to rigid conduit. The 6-foot and 20-ampere limits for using FMC as a grounding path reflect the point at which the impedance becomes too high for reliable overcurrent device operation during a ground fault. Beyond these limits, the fault current through the FMC may not be high enough to trip the breaker quickly, creating a shock hazard.

What plan reviewers look for

Plan reviewers check the electrical drawings for FMC connections and verify each use complies with the permitted locations. They measure the FMC length shown on equipment connection details. For FMC runs over 6 feet or circuits over 20 amperes, they verify a separate equipment grounding conductor is specified in the conduit. They check that FMC is not specified in wet locations without wet-rated conductors and moisture-tight fittings. They verify connector temperature ratings match the installation. For motor connections, they verify the FMC is specified with the correct trade size for the number and size of conductors.

Common violations

FMC over 6 feet without equipment grounding conductor
A 10-foot length of FMC connects a rooftop unit to a junction box on a 30-ampere circuit. No separate equipment grounding conductor is specified. Both the length (over 6 feet) and the circuit size (over 20 amperes) require a separate EGC inside the FMC.
FMC specified in outdoor wet location
FMC with standard conductors is specified for an outdoor connection to a condensing unit. Section 348.12(1) prohibits FMC in wet locations unless the conductors are approved for wet conditions and the installation prevents water entry. Liquidtight flexible metal conduit (LFMC, Article 350) is the correct choice for outdoor wet locations.
Compliance tip
On equipment connection details, specify the FMC length (6 feet maximum if relying on FMC as the grounding path) and note whether a separate EGC is required. For outdoor or wet-location flexible connections, specify LFMC instead of FMC. Include the FMC trade size and conductor fill on the connection detail.
Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

110.14Electrical ConnectionsNEC 2023250.122Equipment Grounding Conductor SizingNEC 2023342.10Uses Permitted for Intermediate Metal Conduit (IMC)NEC 2023

Related articles

Electrical Plan Review Checklist: 10 Issues to Catch Before Submittal