Code Reference
ElectricalNESC 2023

Section 9/Grounding Methods for Electric Supply and Communications Facilities

NESC Section 9 (Rules 091 through 099) covers grounding electrodes, grounding conductors, and connection methods for supply stations, overhead lines, and underground systems.

What this section requires

NESC Section 9 establishes grounding requirements for electric supply and communications facilities. Rule 092 specifies where grounding connections must be made, including at each supply station, at intervals along distribution lines, and at equipment housings. Rule 093 covers grounding electrodes: driven ground rods must be at least 8 feet long and driven to their full length, and where a single rod does not achieve 25 ohms resistance, a supplemental electrode must be installed. Rule 094 specifies grounding conductor materials and sizes. Rule 095 addresses grounding conductor current-carrying capacity, which must be adequate for the maximum fault current and fault duration. Rule 096 covers continuity requirements for grounding systems, ensuring connections are permanent and not easily interrupted by physical damage or corrosion.

Why this section exists

Grounding on the utility side of the meter serves different purposes than premises wiring grounding under the NEC. Supply station grounding must handle fault currents that are orders of magnitude larger than building-side faults, limit ground potential rise (GPR) to protect people near the station during faults, and stabilize system voltages across the distribution network. The IEEE 80 grounding grid design procedure is used to implement these NESC requirements at substations, with step and touch voltage limits governing the grid geometry. The 25-ohm electrode resistance threshold ensures adequate fault current return and reliable protective relay operation.

What plan reviewers look for

Plan reviewers check substation grounding plans for electrode locations, conductor sizes, and connection details. They verify that the grounding grid conductor size is adequate for the available fault current and clearing time. They check that all equipment housings, fences, structural steel, and above-grade metallic structures within the station are bonded to the grounding grid. For distribution line grounding, they verify multi-grounded neutral connections at the required intervals. For overhead line designs, they check that pole ground connections are shown where required and that conductor clearances per Rule 23 account for the grounding configuration.

Common violations

Single ground rod without resistance verification
A substation grounding plan shows individual ground rods at equipment locations without a resistance test requirement. Rule 093 requires that if a single electrode does not achieve 25 ohms or less, a supplemental electrode must be installed. The plan should specify resistance testing and supplemental electrode provisions.
Grounding conductor undersized for fault current
A substation ground grid uses 4/0 copper conductors, but the available fault current and clearing time require a larger conductor to avoid fusing during a fault. The grounding conductor must be sized per Rule 094 and IEEE 80 to carry the maximum fault current for the backup clearing time without damage.
Compliance tip
Show the complete grounding plan with grid conductor size, rod locations, and connection details. Reference the soil resistivity study and the IEEE 80 calculations that support the grid design. Specify the target ground resistance and testing requirements. Show all bonding connections to equipment, fences, and structural elements within the station.
Callout automatically checks your drawings against NESC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

23Clearances of Supply and Communication LinesNESC 202312Grounding Grid Design ProcedureIEEE 80-2013250.50Grounding Electrode SystemNEC 2023