Code Reference
ElectricalNFPA 70E

Section 120.5/Establishing an Electrically Safe Work Condition

NFPA 70E Section 120.5 defines the six-step lockout/tagout process for de-energizing equipment and verifying absence of voltage.

What this section requires

The process for establishing an electrically safe work condition includes six steps: (1) identify all sources of electrical supply, (2) disconnect the load and then open the disconnecting devices for each source, (3) where possible, visually verify that blades are open or draw-out breakers are in the disconnected position, (4) apply lockout/tagout devices, (5) test each conductor with an adequately rated voltage detector to verify absence of voltage, and (6) where the possibility of induced voltages or stored energy exists, ground all circuit conductors. The voltage test instrument must be verified on a known source before and after each use.

Why this section exists

Electrical fatalities most often occur when workers believe equipment is de-energized but it is not. The six-step process prevents this by requiring systematic identification of all sources (including backfeed from generators, UPS systems, and solar PV), positive disconnection with visual verification, lockout/tagout to prevent re-energization, and testing to confirm zero voltage. Each step addresses a specific failure mode that has caused fatal incidents.

What plan reviewers look for

Plan reviewers check that the electrical design supports the lockout/tagout process. This includes lockable disconnect switches at every equipment location, clear labeling of all energy sources, and access for voltage testing. For equipment with multiple sources (utility plus generator, or utility plus solar), all disconnect locations must be identifiable and accessible.

Common violations

No lockable disconnect at equipment
Equipment requiring maintenance does not have a lockable disconnect within sight. Workers cannot complete step 4 (apply lockout device) without a lockable means of disconnection at the equipment.
Multiple sources not identified on drawings
A building with both utility and generator power does not clearly identify both source disconnects on the one-line diagram. Step 1 requires identification of all sources, which depends on clear documentation.
Compliance tip
Provide lockable disconnects at every equipment location. Label all energy sources on the one-line diagram. For dual-source equipment, show both disconnect locations. Reference NFPA 70E in the electrical specifications for the owner's lockout/tagout program.
Callout automatically checks your drawings against NFPA 70E and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

130.5Arc Flash Risk AssessmentNFPA 70E130.7Personal Protective Equipment for Arc FlashNFPA 70E110.3Electrical Safety ProgramNFPA 70E