Code Reference
MechanicalUMC 2021

Section 310.1/Condensate Disposal

UMC 310 covers condensate drain requirements for cooling coils and condensing equipment including traps and secondary drain protection.

What this section requires

Condensate from cooling coils, condensing furnaces, evaporative coolers, and similar equipment must be collected and drained to an approved disposal point. The condensate drain must be trapped with a minimum trap depth equal to the fan static pressure to prevent air from blowing through the drain. Condensate drains must be piped to a floor drain, indirect waste receptor, or the building exterior (not over public walkways). Equipment in attics, on ceilings, or above finished spaces must have a secondary drain pan or a secondary drain connection to prevent water damage from a clogged primary drain.

Why this section exists

Cooling coils generate significant volumes of condensate, especially in humid climates. A clogged condensate drain causes water to overflow the drain pan and damage ceilings, walls, and floors below the equipment. An untrapped drain allows conditioned air to blow out through the drain line, reducing system performance and potentially pulling sewer gases into the air stream. Secondary drain pans and overflow switches provide backup protection that prevents costly water damage.

What plan reviewers look for

Plan reviewers check the mechanical drawings for condensate drain routing from each cooling unit to the disposal point. They verify that traps are shown on the drain line with the trap depth noted. They check for secondary drain pans or secondary drain connections on equipment above finished spaces. They verify the drain terminates at an approved location.

Common violations

Condensate drain not trapped
The condensate drain from a cooling coil does not include a trap. Without a trap, fan pressure blows air through the drain, preventing condensate from draining and spraying water from the drain termination.
No secondary drain protection above finished space
An air handler with a cooling coil is located above a finished ceiling but no secondary drain pan, overflow switch, or secondary drain connection is provided.
Compliance tip
Show condensate drain routing on the mechanical plan from each unit to the disposal point. Detail the trap at each drain connection with the trap depth noted. For equipment above finished spaces, show the secondary drain pan or secondary drain connection routing to a visible location.
Callout automatically checks your drawings against UMC 2021 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

306.5Equipment Access and Service ClearancesIMC 2021504.1Duct Construction and InstallationUMC 2021303.3Combustion Air RequirementsUMC 2021