Code Reference
MechanicalASHRAE 62.1-2022

Section 6.2.6/Exhaust Ventilation

ASHRAE 62.1 Table 6.2.6.2 specifies minimum exhaust airflow rates for spaces requiring direct exhaust, including toilet rooms, kitchens, storage rooms, and parking garages.

What this section requires

Spaces where contaminants are generated at rates exceeding what the supply-air system can dilute must be directly exhausted per Table 6.2.6.2. Toilet rooms and bathrooms require exhaust at 70 CFM per water closet or urinal or 50 CFM per room for private bathrooms. Kitchens (commercial) require exhaust through cooking hoods per ASHRAE 154 or the IMC. Janitor closets and storage rooms require 1.0 CFM per square foot. Parking garages require 0.75 CFM per square foot or a CO-based demand control system. Locker rooms require 0.5 CFM per square foot. The exhaust air must be discharged directly outdoors and not recirculated. Where transfer air from adjacent spaces provides the makeup air for the exhausted space, the transfer opening must be sized adequately and the adjacent space outdoor air must include the transfer component. Exhaust rates from Table 6.2.6.2 are independent of the supply-air outdoor ventilation rates from Table 6.2.2.1.

Why this section exists

Some spaces generate contaminants (odors, moisture, chemical fumes, vehicle exhaust) at concentrations that cannot be adequately diluted by the general ventilation system. Direct exhaust removes these contaminants at the source before they spread to adjacent spaces. Toilet room exhaust prevents odors from migrating into corridors and offices. Kitchen exhaust removes grease-laden air, combustion products, and cooking odors. Parking garage exhaust removes carbon monoxide and nitrogen dioxide from vehicle engines. The exhaust rates in the table are minimum values based on contaminant generation rates and acceptable concentration limits.

What plan reviewers look for

Plan reviewers check the mechanical drawings for exhaust fans serving toilet rooms, kitchens, janitor closets, and parking garages. They verify the exhaust CFM matches Table 6.2.6.2 for the space type and size. They check that exhaust discharges outdoors and not into a return air plenum. They verify makeup air provisions: either dedicated makeup air or transfer air from adjacent spaces with adequately sized transfer openings. For parking garages, they check whether a CO-based demand control system is used as an alternative to constant exhaust. They verify coordination with the IMC exhaust requirements.

Common violations

Toilet room exhaust not provided
A mechanical plan shows supply air to a multi-stall restroom but no exhaust fan or exhaust duct. Toilet rooms require direct exhaust at 70 CFM per water closet or urinal. Without exhaust, odors will migrate to adjacent corridors and offices.
Exhaust recirculated through return air
A toilet room exhaust duct connects to the return air plenum above the ceiling. Exhaust air from spaces listed in Table 6.2.6.2 must be discharged directly outdoors and cannot be recirculated.
Compliance tip
Include an exhaust air schedule on the mechanical drawings listing each exhausted space, its area or fixture count, the required CFM from Table 6.2.6.2, and the fan serving it. Show exhaust discharge points on the roof plan. Show makeup air paths (transfer grilles or dedicated makeup units) and verify the supply system accounts for the transfer air.
Callout automatically checks your drawings against ASHRAE 62.1-2022 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

401.2Ventilation RequiredIMC 20216.2.1Zone Outdoor Air RateASHRAE 62.1-2022501.2Exhaust RequiredIMC 2021

Related articles

8 Things to Check on Every Mechanical Drawing Before You Stamp