Mechanical plan review is one of the most code-dense disciplines in construction. A single HVAC drawing set might need to comply with the IMC, ASHRAE 90.1, ASHRAE 62.1, ASHRAE 55, NFPA 90A/90B, and the local energy code, all at the same time. Here's a working checklist organized by the areas where issues appear most frequently.
1. Equipment schedules
Schedule completeness is the most common source of review comments in mechanical drawings. The schedule is where the design intent meets the spec, and gaps here propagate into every downstream coordination issue.
| Field | Required | Common Issue |
|---|---|---|
| Design airflow (CFM) | All units | Listed for AHUs, missing for FCUs |
| Entering/leaving temps | All cooling units | Leaving temp omitted |
| Cooling capacity | All cooling units | Total shown, sensible missing |
| Heating capacity | All heating units | Usually present |
| Motor HP / electrical | All units | MCA/MOCP often missing |
| Minimum outside air | All ventilation units | Missing or inconsistent with 62.1 calc |
| Efficiency (IEER/SEER/COP) | All units per 90.1 | Most commonly missing field |
| Sound ratings | Where specified | Often deferred to submittals |
2. Ventilation rates (ASHRAE 62.1)
ASHRAE 62.1 ventilation rate compliance requires two things: correct outdoor air calculations and documentation that shows the work. The ventilation rate procedure (Section 6.2) calculates outdoor air based on people (Rp) and area (Ra) components for each zone, then adjusts for system-level efficiency.
Common errors include using occupant density from Table 6.2.2.1 without adjusting for actual anticipated occupancy, forgetting the area-based (Ra) component entirely, and calculating zone-level outdoor air correctly but not performing the system-level calculation for multi-zone systems (Section 6.2.5).
3. Equipment access clearances
IMC Section 306.5 (and manufacturer requirements, which are typically more restrictive) mandate minimum clearances around equipment for service access.
4. Duct sizing and pressure
Duct sizing isn't explicitly prescribed by the IMC, but ASHRAE 90.1 Section 6.5.3 sets maximum fan power limits that indirectly constrain duct sizing. Undersized ducts mean higher static pressure, which means more fan power.
Also verify duct material and construction class. SMACNA construction standards define pressure class and sealing requirements based on static pressure. A 4-inch WG duct system with Class C sealing (or no sealing class noted) will fail a leakage test and waste energy.
5. Refrigerant safety (ASHRAE 15)
Any system using more than a small quantity of refrigerant needs to comply with ASHRAE 15. The key checks: refrigerant quantity doesn't exceed the allowable limit for the occupied space, the mechanical room has the required refrigerant detection system, and ventilation of the mechanical room meets Section 8.11 requirements.
6. Energy code compliance (ASHRAE 90.1)
Beyond equipment efficiency, ASHRAE 90.1 has mechanical-specific requirements that are frequently missed: economizer requirements (Section 6.5.1), simultaneous heating and cooling limits (Section 6.5.2), energy recovery requirements (Section 6.5.6), and demand-controlled ventilation for high-occupancy spaces (Section 6.5.3.7).
7. Fire and smoke protection (NFPA 90A/90B)
Ductwork that passes through fire-rated assemblies needs fire dampers (for fire barriers) or smoke dampers (for smoke barriers), per NFPA 90A. Verify that damper locations are shown on the drawings wherever ducts penetrate rated walls and floor/ceiling assemblies. Also check that duct smoke detection required by Section 6.4.2 of the IMC is shown for systems over 2,000 CFM serving more than one floor.
8. Coordination with other disciplines
Mechanical drawings don't exist in isolation. Check for conflicts with structural elements (ducts routing through beams, equipment loads on non-structural roofs), electrical coordination (disconnect switches, VFD locations, conduit routing), and plumbing (condensate drainage, hydronic piping routing).
Using this checklist
This is a starting point, not an exhaustive list. Every project has jurisdiction-specific requirements, owner-specific standards, and design conditions that affect what to look for. The value of a checklist is that it catches the things that are easy to miss when you're focused on the hard stuff. In mechanical review, there's a lot of hard stuff to focus on.
Code references in this post are based on ASHRAE 90.1-2022, ASHRAE 62.1-2022, IMC 2024, and NFPA 90A 2024. Verify section numbers against your jurisdiction's adopted editions. Callout checks all of these simultaneously on every sheet. start with 50 free credits →