Code Reference
EnergyASHRAE 90.1-2022

Section 6.5.6.1/Exhaust Air Energy Recovery

ASHRAE 90.1 Section 6.5.6.1 requires energy recovery ventilation for systems exceeding outdoor air thresholds by climate zone.

What this section requires

Energy recovery is required when the supply fan airflow rate exceeds the thresholds in Table 6.5.6.1 based on the climate zone and the percent outdoor air at design conditions. For example, in climate zone 5 (Chicago, Denver), energy recovery is required for systems with 70% or more outdoor air at design airflow rates of 750 cfm or more, and for systems with less than 70% outdoor air at higher thresholds. The energy recovery device must have an enthalpy recovery ratio of at least 50% at design conditions. The requirement applies to both heating and cooling energy recovery based on the climate zone.

Why this section exists

Ventilation air represents a significant energy cost: outdoor air must be heated in winter and cooled/dehumidified in summer. Energy recovery devices (enthalpy wheels, plate heat exchangers, heat pipes) transfer energy between the exhaust air stream and the incoming outdoor air stream, recovering 50-80% of the energy that would otherwise be wasted. For buildings with high outdoor air requirements (hospitals, labs, restaurants), energy recovery can reduce HVAC energy consumption by 20-40%.

What plan reviewers look for

Plan reviewers check the mechanical drawings for energy recovery devices on systems exceeding the Table 6.5.6.1 thresholds. They verify the climate zone, supply airflow rate, and percent outdoor air to determine whether energy recovery is required. They check the energy recovery device's rated enthalpy recovery ratio (50% minimum). They verify the device is shown on the air handling unit schedule or the mechanical plan.

Common violations

Energy recovery not provided for high OA system
A laboratory AHU with 100% outdoor air at 5,000 cfm does not include energy recovery. In most climate zones, 100% outdoor air systems above 750 cfm require energy recovery.
Recovery ratio below 50%
The specified energy recovery device has a sensible-only recovery ratio of 45%. Section 6.5.6.1 requires a minimum 50% enthalpy (total) recovery ratio, not just sensible recovery.
Compliance tip
Check Table 6.5.6.1 for every air handling unit on the project. Note the climate zone, supply airflow, and outdoor air percentage. Specify the energy recovery device with the enthalpy recovery ratio on the equipment schedule. Show the device on the mechanical plan with the exhaust and outdoor air connections.
Callout automatically checks your drawings against ASHRAE 90.1-2022 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

C403.1Mechanical Systems ScopeIECC 20216.2.1Zone Outdoor Air RateASHRAE 62.1-20226.5.1Economizer RequirementsASHRAE 90.1-2022