Code Reference
ElectricalNEC 2023

Section 250.24/Grounding Service-Supplied AC Systems

NEC 250.24 requires a grounding electrode conductor and main bonding jumper at the service to connect the grounded conductor to the equipment grounding system and earth.

What this section requires

For AC systems required to be grounded, the grounding connections must be made at each service. Section 250.24(A) requires a grounding electrode conductor (GEC) to connect the grounded service conductor (neutral) to the grounding electrode system. Section 250.24(B) requires a main bonding jumper to connect the grounded conductor to the service equipment enclosure. The GEC must be sized per Table 250.66 based on the size of the largest ungrounded service-entrance conductor. Section 250.24(C) requires that the grounded conductor be routed with the ungrounded conductors and sized not smaller than specified in Table 250.102(C)(1). Section 250.24(D) prohibits grounding connections (neutral-to-ground bonds) on the load side of the service disconnecting means.

Why this section exists

The service grounding connection is the single most critical point in a building's electrical safety system. The main bonding jumper creates the low-impedance fault return path that allows overcurrent devices to clear ground faults quickly. The grounding electrode conductor connects the system to earth, stabilizing voltage during normal operation and providing a path for lightning and surge currents. The prohibition on downstream neutral-to-ground bonds prevents objectionable current on equipment grounding conductors and metallic piping systems.

What plan reviewers look for

Plan reviewers verify that the one-line diagram shows the main bonding jumper at the service equipment and the grounding electrode conductor to the grounding electrode system. They check the GEC size against Table 250.66 based on the service-entrance conductor size. They verify that no neutral-to-ground bonds exist downstream of the main disconnect, particularly in subpanels. For separately derived systems (transformers, generators), they check that grounding complies with Section 250.30 instead of 250.24.

Common violations

Grounding electrode conductor undersized
A 400-ampere service with 500 kcmil copper service-entrance conductors specifies a #4 copper GEC. Table 250.66 requires a #1/0 copper GEC for service conductors over 350 kcmil through 600 kcmil.
Neutral-to-ground bond in subpanel
A subpanel downstream of the main service shows the neutral bus bonded to the enclosure. Section 250.24(A)(5) prohibits grounding connections on the load side of the service disconnect. The neutral and equipment ground must be separated in all downstream panels.
Compliance tip
Show the main bonding jumper, GEC, and grounding electrode system on the one-line diagram. Size the GEC per Table 250.66 and note it on the drawing. Clearly indicate that subpanels have isolated neutral buses. For buildings with multiple services or separately derived systems, show each grounding connection point.
Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

250.122Equipment Grounding Conductor SizingNEC 2023250.30Grounding Separately Derived SystemsNEC 2023250.50Grounding Electrode SystemNEC 2023

Related articles

8 NEC Violations That Show Up on Every Electrical Plan Review