Code Reference
ElectricalNEC 2023

Section 430.52/Motor Branch Circuit Protection

NEC 430.52 establishes maximum overcurrent device ratings for motor branch circuits using FLC tables rather than nameplate current.

What this section requires

Motor branch circuit short-circuit and ground-fault protective devices must be capable of carrying the starting current of the motor. The maximum rating is determined by Table 430.52, which specifies percentages of the motor full-load current (FLC) from Tables 430.248 through 430.250 based on the type of motor and the type of protective device. For an inverse time breaker protecting a standard AC motor, the maximum is 250% of the FLC. If 250% does not correspond to a standard rating, the next standard size up is permitted.

Why this section exists

Motors draw 5-8 times their full-load current during startup. A standard overcurrent device sized to the motor FLC would trip every time the motor starts. The elevated percentages in Table 430.52 allow the breaker to ride through the starting inrush without tripping while still providing short-circuit and ground-fault protection. Overload protection is provided separately by the motor overload relay per Part III of Article 430.

What plan reviewers look for

Plan reviewers verify that motor branch circuit breaker sizes on the panel schedule do not exceed the maximum percentage from Table 430.52. They check that the FLC is taken from the NEC tables (430.248-430.250), not from the motor nameplate. They also verify that the MOCP (Maximum Overcurrent Protective Device) on the mechanical equipment schedule matches the breaker size on the electrical panel schedule.

Common violations

Nameplate current used instead of NEC table FLC
The motor branch circuit breaker is sized based on the motor nameplate amperage. NEC 430.6 requires using the FLC from Tables 430.248-430.250, which may differ from the nameplate value.
MOCP mismatch between mechanical and electrical
The mechanical schedule shows an MOCP of 40 amps but the electrical panel schedule shows a 30-amp breaker for the same equipment. These must match.
Maximum percentage exceeded
A motor branch circuit breaker exceeds the 250% (inverse time) or 800% (instantaneous trip) limit from Table 430.52 for the motor type and protective device type.
Compliance tip
Use the NEC FLC tables (not nameplate) to size motor branch circuit breakers. Cross-reference every motor's MOCP on the mechanical schedule with the corresponding breaker on the electrical panel schedule. Note the Table 430.52 percentage used in the circuit design.

Related NEC requirements

Section 430.6 requires using Table FLC values. Section 430.32 covers motor overload protection (separate from branch circuit protection). Section 430.24 covers conductor sizing for multiple motor circuits. Tables 430.248-430.250 provide the full-load current values.

Callout automatically checks your drawings against NEC 2023 and 43+ other building codes and standards. Each finding includes the exact section reference, severity rating, and suggested resolution.
Try it with 50 free credits

Related sections

240.4Protection of ConductorsNEC 2023310.16Conductor Ampacity TableNEC 2023408.4Panel Schedule Circuit DirectoryNEC 2023